CP1H
Applicable standards CP1H
Refer to the OMRON website or ask your OMRON representative for the most recent applicable standards for each model.
CPU Units CP1H
CPU Unit | Specifications | Model | ||||
---|---|---|---|---|---|---|
CPU type | Power supply |
Output method |
Inputs | Out- puts |
||
CP1H-X CPU Units |
Memory capacity: 20K steps High-speed counters: 100 kHz, 4 axes Pulse outputs: 100 kHz, 4 axes (Models with transistor outputs only) |
AC power supply |
Relay output | 24 | 16 | CP1H-X40DR-A |
DC power supply |
Transistor output (sinking) |
CP1H-X40DT-D | ||||
Transistor output (sourcing) |
CP1H-X40DT1-D | |||||
CP1H-XA CPU Units |
Memory capacity: 20K steps High-speed counters: 100 kHz, 4 axes Pulse outputs: 100 kHz, 4 axes (Models with transistor outputs only) Analog inputs: 4 Analog outputs: 2 |
AC power supply |
Relay output | 24 | 16 | CP1H-XA40DR-A |
DC power supply |
Transistor output (sinking) |
CP1H-XA40DT-D | ||||
Transistor output (sourcing) |
CP1H-XA40DT1-D | |||||
CP1H-Y CPU Units |
Memory capacity: 20K steps High-speed counters: 1 MHz, 2 axes 100 kHz, 2 axes Pulse outputs: 1 MHz, 2 axes 100 kHz, 2 axes |
DC power supply |
Transistor output (sinking) |
12 + line- driver input, 2 axes |
8 + line- driver output, 2 axes |
CP1H-Y20DT-D |
Note: 1. CP1H PLCs are supported by CX-Programmer version 6.1 or higher.
2. Purchase a separately sold Option Unit if you will use RS-232C, RS-422A/485, Ethernet, or LCD.
Options for CPU Units CP1H
Name | Specifications | Model | |
---|---|---|---|
RS-232C Option Board |
Can be mounted in either CPU Unit Option Board slot 1 or 2. |
CP1W-CIF01 | |
RS-422A/485 Option Board |
CP1W-CIF11 | ||
RS-422A/485 (Isolated-type) Option Board |
CP1W-CIF12-V1 | ||
Ethernet Option Board |
Can be mounted in either CPU Unit Option Board slot 1 or 2. * | CP1W-CIF41 | |
LCD Option Board |
Can be mounted only in the CPU Unit Option Board slot 1. | CP1W-DAM01 | |
Memory Cassette |
Can be used for backing up programs or auto-booting. | CP1W-ME05M |
* When using CP1W-CIF41 Ver.1.0, one Ethernet port can be added.
Windows are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or other countries.
Other company names and product names in this document are the trademarks or registered trademarks of their respective companies.
Programming Devices CP1H
Name | Specifications | Model | |||
---|---|---|---|---|---|
Number of licenses |
Media | ||||
FA Integrated Tool Package CX-One Lite Version 4.[] |
CX-One Lite is a subset of the complete CX-One package that provides only the Support Software required for micro PLC applications. CX-One Lite runs on the following OS. OS: Windows 7 (32-bit/64-bit version) / Windows 8 (32-bit/64-bit version)/ Windows 8.1 (32-bit/64-bit version) / Windows 10 (32-bit/64-bit version) CX-One Lite Ver. 4.[] includes Micro PLC Edition CXProgrammer Ver. 9.[]. |
1 license | DVD | CXONE-LT01C-V4 | |
FA Integrated Tool Package CX-One Ver.4.[] |
CX-One is a package that integrates the Support Software for OMRON PLCs and components. CX- One runs on the following OS. OS: Windows 7 (32-bit/64-bit version) / Windows 8 (32-bit/64-bit version)/ Windows 8.1 (32-bit/64-bit version) / Windows 10 (32-bit/64-bit version) CX-One Ver. 4.[] includes CX-Programmer Ver. 9.[]. |
1 license *3 |
DVD | CXONE-AL01D-V4 | |
Programming Device Connecting Cable for CP1W-CIF01 RS-232C Option Board *4 |
Connects Personal Computers, D-Sub 9-pin (Length: 2.0 m) |
For anti-static connectors |
XW2Z-200S-CV | ||
Connects Personal Computers, D-Sub 9-pin (Length: 5.0 m) |
XW2Z-500S-CV | ||||
Connects Personal Computers, D-Sub 9-pin (Length: 2.0 m) | XW2Z-200S-V | ||||
Connects Personal Computers, D-Sub 9-pin (Length: 5.0 m) | XW2Z-500S-V |
*1. CP1H PLCs are supported by CX-Programmer version 6.1 or higher.
CX-One version 2.0).
*2. The CX-One and CX-One Lite cannot be simultaneously installed on the same computer.
*3. Multi licenses (3, 10, 30, or 50 licenses) and DVD media without licenses are also available for the CX-One.
*4. Cannot be used with a peripheral USB port.
To connect to a Personal Computers via a peripheral USB port, use commercially-available USB cable (A or B type,
male).
The following tables lists the Support Software that can be installed from CX-One
Support Software in CX-One | CX-One Lite Ver.4.[] | CX-One Ver.4.[] | |
---|---|---|---|
Micro PLC Edition CX-Programmer | Ver.9.[] | Yes | No |
CX-Programmer | Ver.9.[] | No | Yes |
CX-Integrator | Ver.2.[] | Yes | Yes |
Switch Box Utility | Ver.1.[] | Yes | Yes |
CX-Protocol | Ver.1.[] | No | Yes |
CX-Simulator | Ver.1.[] | Yes | Yes |
CX-Position | Ver.2.[] | No | Yes |
CX-Motion-NCF | Ver.1.[] | No | Yes |
CX-Motion-MCH | Ver.2.[] | No | Yes |
CX-Motion | Ver.2.[] | No | Yes |
CX-Drive | Ver.1.[] | Yes | Yes |
CX-Process Tool | Ver.5.[] | No | Yes |
Faceplate Auto-Builder for NS | Ver.3.[] | No | Yes |
CX-Designer | Ver.3.[] | Yes | Yes |
NV-Designer | Ver.1.[] | Yes | Yes |
CX-Thermo | Ver.4.[] | Yes | Yes |
CX-ConfiguratorFDT | Ver.1.[] | Yes | Yes |
CX-FLnet | Ver.1.[] | No | Yes |
Network Configurator | Ver.3.[] | Yes | Yes |
CX-Server | Ver.4.[] | Yes | Yes |
Note: For details, refer to the CX-One Catalog (Cat. No: R134).
Expansion Units CP1H
Product name |
Inputs | Outputs | Output type | Model | |
---|---|---|---|---|---|
Input Unit | 8 | — | 24 VDC Input | CP1W-8ED | |
Output Units |
— | 8 | Relay | CP1W-8ER | |
Transistor (sinking) | CP1W-8ET | ||||
Transistor (sourcing) | CP1W-8ET1 | ||||
— | 16 | Relay | CP1W-16ER | ||
Transistor (sinking) | CP1W-16ET | ||||
Transistor (sourcing) | CP1W-16ET1 | ||||
— | 32 | Relay | CP1W-32ER | ||
Transistor (sinking) | CP1W-32ET | ||||
Transistor (sourcing) | CP1W-32ET1 | ||||
I/O Units |
12 | 8 | Relay | CP1W-20EDR1 | |
Transistor (sinking) | CP1W-20EDT | ||||
Transistor (sourcing) | CP1W-20EDT1 | ||||
24 | 16 | Relay | CP1W-40EDR | ||
Transistor (sinking) | CP1W-40EDT | ||||
Transistor (sourcing) | CP1W-40EDT1 | ||||
Analog Input Unit |
4CH | — | Input range: 0 to 5 V, 1 to 5 V, 0 to 10 V, ±10 V, 0 to 20mA, or 4 to 20 mA. |
Resolution: 1/6000 |
CP1W-AD041 |
Resolution: 1/12000 |
CP1W-AD042 | ||||
Analog Output Unit |
— | 2CH | Output range: 1 to 5 V, 0 to 10 V, ±10 V, 0 to 20 mA, or 4 to 20 mA. |
Resolution: 1/6000 |
CP1W-DA021 |
— | 4CH | Resolution: 1/6000 |
CP1W-DA041 | ||
Resolution: 1/12000 |
CP1W-DA042 | ||||
Analog I/O Unit |
4CH | 4CH | Input range: 0 to 5 V, 1 to 5 V, 0 to 10 V, ±10 V, 0 to 20 mA, or 4 to 20 mA. Output range: 1 to 5 V, 0 to 10 V, ±10 V, 0 to 20 mA, or 4 to 20 mA. |
Resolution: 1/12000 |
CP1W-MAD44 |
4CH | 2CH | Resolution: 1/12000 |
CP1W-MAD42 | ||
2CH | 1CH | Resolution: 1/6000 |
CP1W-MAD11 | ||
Temperature Sensor Unit |
2CH | — | Sensor type: Thermocouple (J or K) | CP1W-TS001 | |
4CH | — | Sensor type: Thermocouple (J or K) | CP1W-TS002 | ||
2CH | — | Sensor type: Platinum resistance thermometer (Pt100 or JPt100) |
CP1W-TS101 | ||
4CH | — | Sensor type: Platinum resistance thermometer (Pt100 or JPt100) |
CP1W-TS102 | ||
4CH | — | Sensor type: Thermocouple (J or K) 2 channels can be used as analog input. Input range: 1 to 5 V, 0 to 10 V, 4-20 mA |
Resolution: 1/12000 |
CP1W-TS003 | |
12CH | — | Sensor type: Thermocouple (J or K) | CP1W-TS004 | ||
CompoBus/S I/O Link Unit |
8 | 8 | CompoBus/S slave | CP1W-SRT21 |
I/O Connecting Cable CP1H
Name | Specifications | Model |
---|---|---|
I/O Connecting Cable | 80 cm (for CP1W Expansion Units) | CP1W-CN811 |
Note: An I/O Connecting Cable (approx. 6 cm) for horizontal connection is provided with CP1W Expansion Units.
Optional Products, Maintenance Products and DIN Track Accessories
Name | Specifications | Model | |
---|---|---|---|
Battery Set | For CP1H CPU Units (Use batteries within two years of manufacture.) | CJ1W-BAT01 | |
DIN Track | Length: 0.5 m; Height: 7.3 mm | PFP-50N | |
Length: 1 m; Height: 7.3 mm | PFP-100N | ||
Length: 1 m; Height: 16 mm | PFP-100N2 | ||
End Plate | There are 2 stoppers provided with a CJ Unit Adapter as standard accessories to secure the Units on the DIN Track. |
PFP-M |
CJ-series Special I/O Units and CPU Bus Units CP1H
Category | Name | Specifications | Model | |
---|---|---|---|---|
CP1H CPU Unit options |
CJ Unit Adapter | Adapter for connecting CJ-series Special I/O Units and CPU Bus Units (includes CJ-series End Cover and 2 End Plates) |
CP1W-EXT01 | |
CJ1 Special I/O Units |
Analog Input Units |
4 inputs (1 to 5 V (1/10,000), 0 to 10 V (1/20,000), -5 to 5 V (1/20,000), -10 to 10 V (1/40,000), and 4 to 20 mA (1/10,000)) Conversion Period: 20 μs/1 point, 25 μs/2 points, 30 μs/3 points, 35 μs/4 points |
CJ1W-AD042 | |
8 inputs (1 to 5 V, 0 to 5 V, 0 to 10 V, -10 to 10 V, 4 to 20 mA) Resolution: 1/8,000, Conversion speed: 250 μs/ input max. (Can be set to 1/4,000 resolution and 1 ms/input.) |
CJ1W-AD081-V1 | |||
4 inputs (1 to 5 V, 0 to 5 V, 0 to 10 V, -10 to 10 V, 4 to 20 mA) Resolution: 1/8,000, Conversion speed: 250 μs/ input max. (Can be set to 1/4,000 resolution and 1 ms/input.) |
CJ1W-AD041-V1 | |||
Analog Output Units |
4 outputs (1 to 5 V (1/10,000), 0 to 10 V (1/20,000), and -10 to 10 V (1/40,000) Conversion Period: 20 μs/1 point, 25 μs/2 points, 30 μs/3 points, 35 μs/4 points |
CJ1W-DA042V | ||
8 outputs (1 to 5 V, 0 to 5 V, 0 to 10 V, -10 to 10 V) Resolution: 1/4,000; Conversion speed: 1 ms/output max. (Can be set to 1/8000, 250 μs/output.) |
CJ1W-DA08V | |||
8 outputs (4 to 20 mA) Resolution: 1/4,000; Conversion speed: 1 ms/output max. (Can be set to 1/8,000, 250 μs/ output.) |
CJ1W-DA08C | |||
4 outputs (1 to 5 V, 0 to 5 V, 0 to 10 V, -10 to 10 V, 4 to 20 mA) Resolution: 1/4,000, Conversion speed: 1ms/point max. |
CJ1W-DA041 | |||
2 outputs (1 to 5 V, 0 to 5 V, 0 to 10 V, -10 to 10 V, 4 to 20 mA) Resolution: 1/4,000, Conversion speed: 1ms/point max. |
CJ1W-DA021 | |||
Analog I/O Unit | 4 inputs, 2 outputs (1 to 5 V, 0 to 5 V, 0 to 10 V, -10 to 10 V, 4 to 20 mA) Resolution: 1/4000; Conversion speed: 1 ms/point max. (Can be set to 1/8,000, 500 μs/point.) |
CJ1W-MAD42 | ||
Process Input Units |
4 fully universal inputs: Pt100 (3-wire), JPt100 (3- wire), Pt1000 (3-wire), Pt100 (4 wire), K, J, T, E, L, U, N, R, S, B, WRe5-26, PLII, 4 to 20 mA, 0 to 20 mA, 1 to 5 V, 0 to 1.25 V, 0 to 5 V, 0 to 10 V, ±100-mV selectable range, -1.25 to 1.25 V, -5 to 5 V, -10 to 10 V, ±10-V selectable range Potentiometer resolution/conversion speed: 1/256,000 (conversion cycle: 60 ms/4 points), 1/64,000 (conversion cycle: 10 ms/4 points), 1/16,000 (conversion cycle: 5 ms/4 points) |
CJ1W-PH41U * | ||
4 fully universal inputs: Pt100, JPt100, Pt1000, K, J, T, L, R, S, B, 4 to 20 mA, 0 to 20 mA, 1 to 5 V, 0 to 5 V, 0 to 10 V Conversion speed: 250 ms/4 points |
CJ1W-AD04U | |||
4 inputs, B, J, K, L, R, S, T; Conversion speed: 250 ms/4 inputs |
CJ1W-PTS51 | |||
4 inputs, Pt100 Ω (JIS, IEC), JPt100 Ω, Conversion speed: 250 ms/4 inputs |
CJ1W-PTS52 | |||
2 inputs, B, E, J, K, L, N, R, S, T, U, W, Re5-26, PL ±100 mV, Resolution: 1/64,000; Conversion speed: 10 ms/2 inputs |
CJ1W-PTS15 | |||
2 inputs, 0 to 1.25 V, -1.25 to 1.25 V, 0 to 5 V, 1 to 5 V, -5 to 5 V, 0 to 10 V, -10 to 10 V, ±10-V selectable range, 0 to 20 mA, 4 to 20 mA |
CJ1W-PDC15 | |||
Temperature Control Units |
4 loops, thermocouple input, NPN output | CJ1W-TC001 | ||
4 loops, thermocouple input, PNP output | CJ1W-TC002 | |||
2 loops, thermocouple input, NPN output, heater burnout detection function |
CJ1W-TC003 | |||
2 loops, thermocouple input, PNP output, heater burnout detection function |
CJ1W-TC004 | |||
4 loops, platinum resistance thermometer input, NPN output |
CJ1W-TC101 | |||
4 loops, platinum resistance thermometer input, PNP output |
CJ1W-TC102 | |||
2 loops, platinum resistance thermometer input, NPN output, heater burnout detection function |
CJ1W-TC103 | |||
2 loops, platinum resistance thermometer input, PNP output, heater burnout detection function |
CJ1W-TC104 | |||
High-speed Counter Unit |
2 inputs, max. input frequency: 500 kpps | CJ1W-CT021 | ||
Position Control Units |
Pulse train, open collector output, 1 axis | CJ1W-NC113 | ||
Pulse train, open collector output, 2 axes | CJ1W-NC213 | |||
Pulse train, open collector output, 4 axes | CJ1W-NC413 | |||
Pulse train, line driver output, 1 axis | CJ1W-NC133 | |||
Pulse train, line driver output, 2 axes | CJ1W-NC233 | |||
Pulse train, line driver output, 4 axes | CJ1W-NC433 | |||
Space Unit | — | CJ1W-SP001 | ||
ID Sensor Units | For V680 Series, 1 R/W Head | CJ1W-V680C11 | ||
For V680 Series, 2 R/W Heads | CJ1W-V680C12 | |||
For V600 Series, 1 R/W Head | CJ1W-V600C11 | |||
For V600 Series, 2 R/W Heads | CJ1W-V600C12 | |||
CompoNet Master Unit |
Word slaves: 2,048 points, Bit slaves: 512 points | CJ1W-CRM21 | ||
CompoBus/S Master Unit |
CompoBus/S remote I/O, 256 points max. | CJ1W-SRM21 | ||
CJ1 CPU Bus Units |
Controller Link Units |
Wired (shielded twisted-pair cable) | CJ1W-CLK23 | |
Serial Communications Units |
1 RS-232C port and 1 RS-422A/485 port | CJ1W-SCU42 | ||
2 RS-232C ports | CJ1W-SCU22 | |||
2 RS-422A/485 ports | CJ1W-SCU32 | |||
1 RS-232C port and 1 RS-422A/485 port | CJ1W-SCU41-V1 | |||
2 RS-232C ports | CJ1W-SCU21-V1 | |||
2 RS-422A/485 ports | CJ1W-SCU31-V1 | |||
EtherNet/IP Unit | Shielded twisted-pair cable (STP), category 5 or 5e or higher Tag data links and message communications supported |
CJ1W-EIP21 | ||
Ethernet Unit | 100Base-TX | CJ1W-ETN21 | ||
DeviceNetTM Unit | Functions as master and/or slave; allows control of 32,000 points max. per master |
CJ1W-DRM21 | ||
MECHATROLINK-II Position Control Unit |
Control commands sent using MECHATROLINK-II synchronized communications 16 axes max., direct operation from ladder diagram, control modes: position/ speed/torque |
2 axes | CJ1W-NC271 | |
4 axes | CJ1W-NC471 | |||
16 axes | CJ1W-NCF71 | |||
16 axes | CJ1W-NCF71-MA | |||
Fl-net Unit | 100Base-TX | CJ1W-FLN22 | ||
SPU | High-speed Data Storage Unit | CJ1W-SPU01-V2 |
* If a CJ1W-PH41U is used, do not use a CP1H CPU Unit with relay contact outputs or Expansion Units with relay contact outputs.
Note: Refer to the CJ1 catalog (Cat. No. P052) for information on the CJ1 Special I/O Units.
Industrial Switching Hubs CP1H
Product name |
Appear- ance |
Specifications | Accessories | Current con- sump- tion (A) |
Model | ||
---|---|---|---|---|---|---|---|
Functions | No. of ports |
Failure detec- tion |
|||||
Industrial Switching Hubs |
Quality of Service (QoS): EtherNet/IP™ control data priority Failure detection: Broadcast storm and LSI error detection 10/100BASE-TX, Auto-Negotiation |
3 | No | Power supply connector |
0.22 | W4S1-03B | |
5 | No | 0.22 | W4S1-05B | ||||
5 | Yes | Power supply connector Connector for informing error |
0.22 | W4S1-05C |
last update: September 1, 2020